On an Exadata compute/database server, check temperature through the server’s ILOM service processor. CellCLI is for storage cells; it is not the compute server’s sensor interface. Oracle: Exadata ambient temperature monitoring
Ambient intake temperature on one node:
ipmitool sunoem cli "show /SYS/T_AMB"
Look for the value in °C and the sensor’s alarm_status.
List temperature sensors:
ipmitool sdr list | grep -iE 'ipmitool sdr list | grep degrees'
Example:
ipmitool sdr list | grep degrees
T_IN_ZONE0 | 40 degrees C | ok
T_IN_ZONE1 | 43 degrees C | ok
T_IN_ZONE2 | 37 degrees C | ok
T_IN_ZONE3 | 43 degrees C | ok
T_OUT_ZONE0 | 41 degrees C | ok
T_OUT_ZONE1 | 44 degrees C | ok
T_OUT_ZONE2 | 43 degrees C | ok
T_OUT_ZONE3 | 47 degrees C | ok
PS0/T_IN | 44 degrees C | ok
PS0/T_OUT | 47 degrees C | ok
PS1/T_IN | 42 degrees C | ok
PS1/T_OUT | 48 degrees C | ok
T_AMB | 31 degrees C | ok
For sensor readings and thresholds, Oracle ILOM also documents ipmitool sensor; available sensors depend on the server model. Oracle ILOM: Display sensor list · Oracle ILOM: IPMItool commands
Check ILOM health and open hardware problems from the ILOM CLI:
show /System healthshow /System/Open_Problemsshow /SYS/T_AMB
Oracle’s Exadata guidance gives a rack ambient operating range of 5–32 °C, with 21–23 °C as the optimal range. Those are ambient conditions; use each sensor’s reported status and thresholds for component sensors.